YVV(TSE), NYY(VDE) Cu/PVC/PVC(BS)



0.6/1 kV PVC Insulated Multi-Core Cables With Copper Conductor

Code

YVV(TSE), NYY(VDE) Cu / PVC / PVC (BS)

Standards

TS IEC 60502-1 VDE 0271, IEC 502

Technical Data

Minimum bending radius

:

12xD

Maksimum operating temparature 

:

70°C

Maksimum short circuit temperature

 

 

For cross section : 160°C
For cross section  >  : 140°C

Used In

Fixed wiring in dry and damp premises, in conduits on or under plaster and on insulators over plaster, switching and distribution panels.

Structure

1. Copper conducter 3. PVC filler
2. PVC insulation 4. PVC outer sheath

DIMENSIONS AND WEIGHT

ELECTRICAL SPECIFICATIONS

Nominal Cross Section

Overall diameter
(approximate)

Net Weight (approximate)

Standart delivery lengt

Conductor DC
Resistance at 20°C (max.)

Current carrying capacity in
Ground       |          Air     

mm2

mm

kg/km

m

ohm/km

A

A

2 x 1.5 re

10.5

150

80

12.1

32

20

2 x 2.5 re

11.5

190

90

7.41

42

27

2 x 4 re

13.0

260

90

4.61

54

37

2 x 6 re

14.0

320

100

3.08

68

48

2 x 10 rm

14.5

460

100

1.83

90

66

2 x 16 rm

18.0

620

120

1.15

116

89

3 x 1.5 re

11.0

175

90

12.1

26

18

3 x 2.5 re

12.5

240

90

7.41

34

25

3 x 4 re

14.0

320

90

4.61

44

34

3 x 6 re

15.0

400

100

3.08

56

43

3 x 10 rm

17.0

550

110

1.83

75

60

3 x 16 rm

20.0

800

120

1.15

98

80

4 x 1.5 re

12.0

200

90

12.1

26

18

4 x 1.5 re

13.5

280

90

7.41

34

25

4 x 4 re

15.0

360

100

4.61

44

34

4 x 6 re

16.0

480

110

3.08

56

43

4 x 10 rm

18.0

680

120

1.83

75

60

4 x 16 rm

21.0

1000

130

1.15

98

80

re : Solid conductor - rm : Stranded conductor - D : cable overall diameter (mm)