NVV, 05VV-U, 05VV-R (TSE), NYM (VDE), Cu/PVC/PVC(BS)
Code
NVV, 05VV-U, 05VV-R (TSE), NYM (VDE), Cu / PVC / PVC(BS)
F: Thin Multi Wire Conductor.
Standards
TS 9759, VDE 0281, BS 6004, IEC 227
Technical Data
Maximum operating temperature
:
70°C
Maximum short circuit temperature
160°C
Current carriying capacity values given below
are rated at 30°C ambient temperature.
Used In
Fixed wiring in dry and damp premises, in conduits on or under plaster and on insulators over plaster, switching and distribution panels.
Structure
DIMENSIONS AND WEIGHT
ELECTRICAL SPECIFICATIONS
Nominal Cross Section
Overall diameter (approximate)
Net Weight (approximate)
Standart delivery lengt
Conductor DC Resistance at 20°C (max.)
Current Carrying Capacity in air
mm2
mm
kg/km
m
ohm/km
A
2 x 1.5 re
8.8
110
100
12.1
18
2 x 2.5 re
10.0
150
7.41
26
2 x 4 re
11.0
220
4.61
34
2 x 6 re
12.0
260
3.08
44
2 x 10 rm
16.0
430
1.83
61
2 x 16 rm
18.0
620
1000
1.15
82
3 x 1.5 re
9.0
130
3 x 2.5 re
10.5
180
3 x 4 re
250
3 x 6 re
13.5
350
3 x 10 rm
16.5
530
3 x 16 rm
20.0
800
4 x 1.5 re
4 x 2.5 re
11.5
4 x 4 re
13.0
320
4 x 6 re
15.0
450
4 x 10 rm
18.5
660
4 x 16 rm
22.0